Under Manual mode, wait until the process is at steady state.
-
Next, introduce a step change in the input.
-
Based on the output, obtain an approximate first order process with a time
constant t delayed by tDEL
units from when the input step was introduced.
The values of t and tDEL
can be obtained by first recording the following time instances:
t0 |
= |
time when input step was initiated |
t2 |
= |
time when half point occurs |
t3 |
= |
time when 63.2% point occurs |
-
From the measurements based on the step test: t0, t2,
t3,
A
and B, evaluate the following process parameters:
t1 = (t2 - ln(2) t3)/(1
- ln(2))
t = t3 - t1
tDEL = t1 -
t0
K = B/A
-
Based on the parameters K, t and tDEL,
the following formulas prescribe the controller parameters Kc,
tI
and tD: